Monday, August 30, 2010

Thermocouple Application Note

Unusual Thermocouple Application


Our customer's client had a large spa facility. The controls had been located near the spa, but the client felt they should be moved to a more benign environment, several hundred feet away. The system included four thermocouples. Sending thermocouple signals this distance is expensive, since thermocouple wire (not copper) must be used. Even more basic, sending weak millivolt signals hundreds of feet leaves them subject to interference and signal degradation.

To boost the signals, four standard thermocouple transmitters (our Model JH4130) were added near the spa. Their 4-20mA current signals easily traveled the distance with no degradation. The system designers opted not to change the control system, so it was necessary to convert the current signals back to their original thermocouple voltages. "Reverse" thermocouple transmitters, 4-20mA input, thermocouple output, were needed.

We provided them. We modified our Model JH4300 DC input, DC output transmitters to have the proper millivolt outputs. The most interesting challenge was, the millivolt outputs needed to be connected to thermocouple wires (not copper) for proper connection to the system's thermocouple inputs. This called for the reverse of cold junction compensation (we called it "cold junction un-compensation"). A temperature sensor embedded in the output terminals and some properly-designed circuitry solved the problem

Temperature Transmitters & Signal Conditioners - our web site: http://www.jhtechnology.com/

Sunday, June 13, 2010

Custom Designs

A Very Special Special

A well-known company needed to duplicate a thermocouple alarm they had bought from Action Instruments decades ago. Action was no longer able to provide it so they turned to us.

Action's original "Action Pak" line (Action's trademark) once included alarm modules with extra options such as retransmitting outputs and remote setpoint inputs. 20-pin headers (pin bases) were required to provide the extra connections. As far as we are aware these headers are no longer available.

Our customer's requirement was a nonstandard version of one of those alarms. We replied that we could provide the same function but with a different connection arrangement. This was not acceptable - it was for a nuclear power application and they could not vary the system design. Only one piece, but they were willing to pay for it.

Once again we got lucky. In 1995 we had purchased some 20 pin headers for another customer's need and had a handful left. Our customer bought one (couldn't convince them to buy a spare) - even sent an inspector to Florida to do a source inspection. That was 2008. In 2009 they again bought one and just now ordered two more! Possible future problem - after this order we have only five headers left.

(Note: We do not sell nuclear-approved products. This alarm was sold as "standard commercial quality" for a noncritical application.)

Technical detail: the custom alarm module has two retransmitting 0-1V analog outputs, one proportional to temperature and the other proportional to the setpoint. Our customer was able to supply us with Action's specifications and we designed it to be functionally identical. Here's the functional diagram.



If you have special requirements let us know. Phone (941) 927-0300 or toll-free (800) 808-0300.



Sunday, May 23, 2010

Application Note

Detect Thermocouple Failure Without Upsetting the Process

One from the archives. Our customer needed to alarm on thermocouple failure without shutting down the process.

Thermocouple instruments commonly include upscale burnout indication. If the thermocouple breaks or fails open-circuit the instrument's output goes high, just as if the temperature had gone out of control. This often is used to insure failsafe failure, shutting the process down and sounding an alarm.

Our customer, a utility, needed an overtemperature shutdown on a monitored water temperature. They also wanted to trip an alarm upon thermocouple failure but without interrupting the process. We were able to suggest a simple dual-trip alarm setup to do this.

Our thermocouple instruments, like most others, offer a downscale burnout option. (Thermcouple failure causes the output to go low instead of high.) Using a dual-trip alarm, we set trip #1 for HI trip and trip #2 for LO. The HI trip, of course, was used to shut the process down on excessive temperature. The LO trip was set below freezing. Its relay would trip when the thermocouple failed but never under normal operation.